Appendix H (cont'd.)
NPT NPA POINT DESCRIPTION RANGE/VALUE UNIT
ADI 19 System KW 0 to Span (in Technologic User Setup Menu) KW
ADI 20 Pump #1 Power 0 to Span (in Technologic User Setup Menu) KW
ADI 21 Pump #2 Power 0 to Span (in Technologic User Setup Menu) KW
ADI 22 Pump #3 Power 0 to Span (in Technologic User Setup Menu) KW
ADI 23 Pump #4 Power 0 to Span (in Technologic User Setup Menu) KW
ADI 24 Pump #5 Power 0 to Span (in Technologic User Setup Menu) KW
ADI 25 Pump #6 Power 0 to Span (in Technologic User Setup Menu) KW
ADI 26 System Differential Pressure 0 to Span (in Technologic User Setup Menu) PSI
ADI 27 Supply Temperature Sensor 0 to Span (in Technologic User Setup Menu) F°
ADI 28 Return Temperature Sensor 0 to Span (in Technologic User Setup Menu) F°
ADI 29 Setpoint #1 0 to Span (in Technologic User Setup Menu)
ADI 30 Setpoint #2 0 to Span (in Technologic User Setup Menu)
ADI 31 Setpoint #3 0 to Span (in Technologic User Setup Menu)
ADI 32 Setpoint #4 0 to Span (in Technologic User Setup Menu)
ADI 33 Setpoint #5 0 to Span (in Technologic User Setup Menu)
ADI 34 Setpoint #6 0 to Span (in Technologic User Setup Menu)
ADI 35 Setpoint #7 0 to Span (in Technologic User Setup Menu)
ADI 36 Setpoint #8 0 to Span (in Technologic User Setup Menu)
ADI 37 Setpoint #9 0 to Span (in Technologic User Setup Menu)
ADI 38 Setpoint #10 0 to Span (in Technologic User Setup Menu)
ADI 39 Setpoint #11 0 to Span (in Technologic User Setup Menu)
ADI 40 Setpoint #12 0 to Span (in Technologic User Setup Menu)
ADI 41 Setpoint #13 0 to Span (in Technologic User Setup Menu)
ADI 42 Setpoint #14 0 to Span (in Technologic User Setup Menu)
ADI 43 Setpoint #15 0 to Span (in Technologic User Setup Menu)
ADI 44 Setpoint #16 0 to Span (in Technologic User Setup Menu)
ADI 45 Pump #1 Speed 0 to 100 %
ADI 46 Pump #2 Speed 0 to 100 %
ADI 47 Pump #3 Speed 0 to 100 %
ADI 48 Pump #4 Speed 0 to 100 %
ADI 49 Pump #5 Speed 0 to 100 %
ADI 50 Pump #6 Speed 0 to 100 %
ADI 51 Lead Pump Number 1 to Pump # (in Technologic User Setup Menu)
ADI 52 Active Zone Number 1 to Zone # (in Technologic User Setup Menu)
ADI 53 System Operation Mode 0=Manual,1=Auto, 2=Auto Bypass, 3=Manual Bypass
ADI 54 Bypass Valve Position 0 to 100, 0 = Closed 100 = Open %
ADI 55 Chiller #1 Flow 0 to Span (in Technologic User Setup Menu)
ADI 56 Chiller #2 Flow 0 to Span (in Technologic User Setup Menu)
ADI 57 Chiller #3 Flow 0 to Span (in Technologic User Setup Menu)
ADI 58 Chiller #4 Flow 0 to Span (in Technologic User Setup Menu)
ADI 59 Chiller #5 Flow 0 to Span (in Technologic User Setup Menu)
ADI 60 Chiller #6 Flow 0 to Span (in Technologic User Setup Menu)
ADI 61 Chiller #1 DP 0 to Span (in Technologic User Setup Menu)
ADI 62 Chiller #2 DP 0 to Span (in Technologic User Setup Menu)
ADI 63 Chiller #3 DP 0 to Span (in Technologic User Setup Menu)
ADI 64 Chiller #4 DP 0 to Span (in Technologic User Setup Menu)
ADI 65 Chiller #5 DP 0 to Span (in Technologic User Setup Menu)
ADI 66 Chiller #6 DP 0 to Span (in Technologic User Setup Menu)